top of page

Electromagnetic Compatibility

Knowledge Base

The following chapters are thought of as free education for those of you out there, who have to deal with EMC and electronics design.

We wrote down some of the most essential theoretical knowledge, which you need for mastering EMC. If you wish that we add a specific topic or if you have any questions: Please write us info@academyofemc.com.

 

1  The Decibel

The decibel is defined as a ratio of two quantities, typically power, voltage, or current. In the field of EMC, the decibel must be understood. Here are the most important points:

Gain [dB] and Loss [dB].

Let's have a look at the amplifier or damping network below.

Amplifier or damping network

 

The power, voltage, and current gain of this network can be expressed in [dB] as [1.1]:

Gain dB calculation

 

If R1 and R2 are equal (typically 50Ω), then the following term is 0:

Decibel with equal resistance

 

And we can write the following for power/voltage/current gain:

Power to decibel

 

Points to remember when it comes to the calculation of gain and loss in decibel:

  • Amplification. If P2 is bigger than P1, the gain value in [dB] is positive. This means if there is amplification, the power gain in [dB] is positive.

  • Damping. If P2 is smaller than P1, the gain value in [dB] is negative. This means if there is a power loss, the power gain in [dB] is negative.

  • Cut-off Frequency. At the cut-off frequency, the output power (P2) is half the input power (P1). And the power/voltage/current gains are all -3dB.

Cut-off frequency loss

  • Ratio to [dB]. If power increases by factor 2, the power/voltage/current gains increase by +3dB. If power increases by factor 10, the power/voltage/current gains increase by +10dB. To get an overview, have a look at our power/voltage/current ratios table below.

 

 

Absolute Levels [dBm, dBµV, dBµA].

The most common absolute power, voltage and current levels in EMC are [dBm], [dBµV] and [dBµA]. They are calculated like this [1.1]:

 

Absolute power levels dB

 

The most common absolute power, voltage and current levels in EMC are [dBm], [dBµV] and [dBµA]. They are calculated like this:

 

dBm, dBuV, dBuA

 

For example, a negative dBm-value means that the power level is <1mW. 0dBm = 1mW and a dBm-value bigger than 0 means that the power is higher than 1mW. The same for dBµV and dBµA: 0dBµV = 1µV (0dBµA = 1µA), a negative dBµV-value means <1µV, and a positive dBµV-value means >1µV.

 

dBm, dBuV, dBuA table

 

 

Conversion formulas and tables.

Find below tables and formulas to convert between the different dB-units and from linear ratio values to dB-values and vice versa. In addition, you can download an Excel sheet, which contains conversion calculations and more [1.2].

dB, dBV, dBuV, dbA, dBuA, dBm unit conversion table
V/m, A/m, dBuV/m, dBuA/m, dBmW/m2, dBpT, mT unit conversion table field strength
Linear ratio to dB. Power vs. Voltage vs. Curent ratio in dB.
1 - Decibel
Gain and Loss
Absolute Levels
Unit Conversion
EMC an Frequency

2  Frequency & Wavelength

It is fundamental that professional engineers in the field of EMC understand the basics of signal frequency f [Hz] and wavelength λ [m]:

EMC and Frequency.

In general, EMC issues occur with signals of frequency > 9kHz. This is the reason why most EMC Standards do not consider signals with < 9kHz.

  • Conducted Emission. Conducted emissions tend to occur at f < 30MHz.

  • Radiated Emission. Radiated emissions tend to occur at f > 30MHz. 

Wavelength: Calculation.

The frequency f of a sinusoidal signal and its wavelength λ [m] have the following relationship [2.1]:

How to calculate wavelength?

 

Whereas v [m/sec] is the propagation velocity of the signal and f [Hz] the frequency of the signal.

What is a wavelength?

 

 

Wavelength of signals traveling long blank wires vs. cables & PCB traces.

It is important to understand that the signal propagation velocity v [m/sec] depends on the transport medium through which the electromagnetic field is traveling. Therefore, the same signal with the same frequency f [Hz] has a different wavelength λ [m] in a blank wire (surrounded by air) than in a cable or PCB trace (surrounded by insulation material).​ The wavelength λ [m] is calculated the following way [2.1]:

Wavelength vs. frequency formula. Wavelength in cable and PCB trace vs. air.

 

where v is the signal propagation velocity in [m/sec], c is the speed of light (3E8 [m/sec]), f is the frequency of the sinusoidal signal in [Hz], εr is the relative permittivity and μr is the relative permeability of the media through which the electromagnetic field is propagating. VF is called the velocity factor.

  • Wavelength in a blank wire. The wavelength λ of a signal with frequency f along a blank wire (or antenna surrounded by air) depends only on the speed of light c and the signal frequency f (v=c, because εr = 1 and μr =1 and therefore VF=1) [2.1]:

Wavelength in air (blank wire).

  • Wavelength in cables and PCB traces. The wavelength λ of a signal with frequency f along an insulated copper wire or a cable or a Printed Circuit Board (PCB) trace is [2.1]:

Wavelength calculation for cables and PCB traces

 

Where c is the speed of light (3E8 [m/sec]), f is the signal frequency [Hz], εreff the effective dielectric constant (relative permittivity) through which the electromagnetic wave is propagating. The effective dielectric constant εreff is defined as the uniform equivalent dielectric constant for a transmission line, even in presence of different dielectrics (e.g. FR-4 and air for a microstrip line, see picture below).
The relative permeability μr is assumed to be equal to 1.0 for cables and PCBs because the insulation materials are non-magnetic. Thus, the velocity factor VF depends primarily on the effective relative permittivity (also called effective dielectric constant) εreff of the insulation or PCB material.

The calculation of the effective dielectric constant εreff [1] depends on the insulation material and the geometry of the transmission line (e.g. ribbon cable, microstrip, coplanar waveguide, etc.), because the amount of the electric field lines in the different media depending on the geometry of the transmission line (e.g. see the microstrip line below).

Microstrip line, field lines, effective dielectric constant

The Excel sheet below contains a calculator for calculating the effective dielectric constant εreff [1] (effective permittivity) for some of the most common transmission lines:

  • PCB-traces. Microstrip, stripline, coplanar waveguide with a reference plane.

  • Cables. Ribbon cable, twisted pair.

 

 

The velocity factor VF [1] of a transmission medium is the ratio of the velocity v [m/sec] at which a wavefront of an electromagnetic signal passes through the medium, compared to the speed of light in vacuum c [3E8m/sec]: VF=v/c. Thus, the smaller the velocity factor VF [1], the smaller the wavelength λ [m]. The table below shows the approximate velocity factors for different insulation and PCB materials and different transmission line types [2.2, 2.3, 2.4].

Effective dielectric constant and velocity factor for cable and PCB traces.

 

The table below shows some rough approximations of wavelengths in different conductors (cables, PCBs) compared to free-space (air). Possible assumptions for wavelength λ in PCBs (FR-4) and cables are:

  • PCB. λPCB≈0.5*λair (assumption εreff ≈3.0...4.5 → VF≈0.5).

  • Cables. λCable≈0.7*λair (assumption εreff ≈1.5...3.0 → VF≈0.7).

Wavelength air vs. cable vs. PCB
2 - Wavelength
l calculation
l air vs. conductor

 


3  Time- vs. Frequency-Domain

 

Electrical signals - periodic or non-periodic - can be measured in the time domain (e.g. with an oscilloscope) or in the frequency domain (e.g. with a spectrum analyzer). This means that an electrical signal can be described either in the time-domain or in the frequency-domain. The time-domain representation helps you to determine the signal integrity (ringing, reflections), whereas the frequency domain representation helps you to determine at which frequencies a signal may lead to radiated emissions.

Fourier Analysis.

Fourier analysis is an integral transform and refers to the mathematical principle that every signal can be represented by the sum of simple trigonometric functions (sine, cosine, etc.). The Fourier analysis enables a transformation of a signal in the time domain x(t) to a signal in the frequency domain X(ω), where ω=2𝝅f (notation: x(t)○─●X(ω)). In other words, a Fourier analysis is a mathematical operation for calculating the frequency-domain representation (frequency spectrum) of a signal in the time-domain.

The picture below shows a representation of a square wave signal (1V amplitude) with the sum of only 4 harmonic sine waves and a direct current (DC) component of 0.5V. For the representation of an ideal square wave, an indefinite number of sine waves would be necessary (because the rise- and fall-time of an ideal square wave is 0sec).

Square wave representation with fourier series / transform sine waves.

The different variants of integral transforms are presented in the list below. All variants have in common that they present the necessary math for converting a signal from the time- to the frequency-domain and vice versa: X(ω)─○x(t). Every integral transform variant has its own field of application.

  • Fourier series. Time signal = continuous, periodic. Frequency spectrum = discrete. Formulas for the calculation of the complex Fourier coefficients cn of a signal x(t) are presented below [3.1]:

Fourier series formula
Complex fourier series coefficients formula
Fourier series first harmonic frequency

 

T is the period length of the signal x(t) in [sec], f0 is the first harmonic of the signal x(t) in [Hz], ω0 is the first harmonic of the signal x(t) in [rad], j=√(-1) is the complex number and n stands for the n-th harmonic frequency [0, 1, 2, ...].

  • Fourier transform. Time signal = continuous, non-periodic. Frequency spectrum = continuous. Formulas of the Fourier transform of a signal x(t) (left) and the inverse-Fourier transform (right) are given below [3.2]:

Fourier transform formula
Inverse Fourier transform formula

 

X(ω) is the Fourier transform (spectrum) of x(t), ω is the frequency in [rad], j=√(-1) is the complex number and t the time in [sec].

  • Discrete Fourier transform (DFT). Time signal = discrete, periodic. Frequency spectrum = discrete. The DFT is also applied to non-periodic signals in the time domain by periodically continuing the non-periodic signals in order to make them computable with the DFT. The DFT is by far the most common method of modern Fourier analysis. The Fast Fourier Transformation (FFT) is a fast algorithm for calculating the DFT (in case the bock length N is a power of two) [3.3].

Discrete Fourier Transform (DFT) formula
FourierTransformDiscreteDFTInverse.PNG
Digital Fourier Transform (DFT) frequency and sampling time

 

X is the spectrum of x and X[k] is the k-th sample of the spectrum at ωk. x[n] is the n-th sample of the discrete time signal, which is sampled with the sampling time Ts [sec] and the sampling frequency fs [Hz].

  • Discrete-time Fourier transform (DTFT). Time signal = discrete, non-periodic. Frequency spectrum = continuous. The DTFT can be viewed as the form of the DFT when its length N approaches infinity [3.4].

Discrete-Time Fourier Transform (DTFT)
Inverse Discrete-Time Fourier Transform (DTFT)
Discrete-Time Fourier Transform frequency and sampling rate.

 

X is the spectrum of xx[n] is the n-th sample of the discrete time signal, which is sampled with the sampling time Ts [sec] and the sampling frequency fs [Hz].  denotes the continuous normalized radian frequency variable [-π...+π].  is the product of the radian frequency ω [rad] and the sampling time Ts. ​

  • Laplace transform. The Laplace transformation belongs - like the Fourier analyses - to the group of integral transformations. It is mentioned here for the sake of completeness. The Laplace transform is used for system analysis (e.g. control systems, filters), whereas the Fourier transform is used for signal analysis [3.5].

Laplace transform formula
Laplace transform variable

 

X is the Laplace transform of x. s=σ+ is a complex variable with a real part σ and a imaginary part with the radian frequency ω [rad]. In case of σ=0, the Laplace transform reduces to the Fourier transform.

  • Z-transform. The Z-transform is the time-discrete counterpart to the Laplace transform with z = e^(sTsampling) = e^(+jω)Tsampling) [3.6].

Z-transform formula
Z-transform to Laplace transform

 

X is the Z-transform of x. z is a complex variable. x[n] is the n-th sample of the discrete time signal, which is sampled with the sampling time Ts [sec] and the sampling frequency fs [Hz].

Fourier analysis: Fourier series vs. Fourier transform vs. discrete Fourier transform (DFT) vs. discrete-time fourier transform (DTFT)

Spectra of digital waveforms.

Waveforms of primary importance in electronic circuits are clock and data signals. Digital signals in the time domain can be represented by trapezoid-shaped pulses with a period time T [sec], a pulse width tpw [sec], a rise-time tr [sec] and a fall-time tf [sec]. The two pictures below show an extract of a digital waveform in the time-domain and an amplitude frequency spectrum of a digital signal with its envelope curve [3.7].

Digital signal waveform
Frequency spectrum of digital signal

The frequency spectrum envelope of a trapezoid-waveform signal compared to an ideal square wave signal is shown below. It can be seen, that there is no -40dB drop-off for the ideal square wave. Instead, the frequency spectrum envelope of an ideal square wave drops constantly with -20dB/decade.

Frequency spectrum of trapezoid vs. ideal square wave

The picture below compares the frequency spectrum of two trapezoid waveforms with different pulse-width tpw [sec], but with identical periodicity T [sec], rise- and fall-time tr [sec] and tf [sec] and amplitude A [V]. It can be seen how the duty-cycle D=tpw/T [%] of a digital signal influences the frequency spectrum. However, it is remarkable that a clock signal with a 90% duty-cycle has a lower amplitude of the first harmonic than a clock signal with a 50% duty-cycle (of the same frequency [Hz] and with the same rise/fall-time [sec]). The clock signal with a 90% duty-cycle has more power, but this power adds to the DC component (0 Hz).

Frequency spectrum of trapezoid with different pulse-width (duty cycles)

The picture below compares the frequency spectrum of two trapezoid waveforms with different rise- and fall-time tr [sec] and tf [sec], but with identical periodicity T [sec], pulse-width tpw [sec] and amplitude A [V]. It can be seen that a reduction of the rise- and fall-time leads to lower amplitudes at the higher frequencies in the spectrum (and therefore to potentially lower radiated emissions). In this example, an increase of the rise- and fall-time [sec] by factor 10, reduces the amplitude of the high-frequency harmonics ( f > 32MHz) also by factor 10 (20 dB).

Frequency spectrum with different rise- and fall-time

Bandwidth of digital signals.

Bandwidth [Hz] of a digital signal means: What is the highest significant sine-wave frequency component in the digital signal? Significant in this case means that the power [W] in the frequency component is bigger than 50% of the power in an ideal square wave's signal with the same amplitude A [V] and duty-cycle D=tpw/T  [%]. A drop in 50% of the power [W] is the same as a drop of 70% in amplitude [V] or a drop of 3dB.

The rule of thumb for calculating the bandwidth [Hz] - or the highest significant sine wave frequency - of a trapezoid digital signal is [3.8]:

Bandwidth of digial singals

Where t10%-90% is the rising- or fall-time (whichever is smaller) from 10% to 90% of the slope of a digital signal in [sec].

The picture below shows the frequency spectrum envelop curves of an ideal square wave (t10%-90%=0) and a real waveform (trapezoid with t10%-90%0). The bandwidth of the real waveform can be found at f=0.35/t10%-90%. Note: It is assumed that there is no ringing in the real waveform. In case of ringing, the frequency spectrum envelope for f>1/(πt10%-90%would not drop off with -40dB/decade.

DigitalSignal_Spectrum_Bandwidth.PNG
3 - Time/Frequency Domain
Fourier analysis
Digital waveforms spectra
Bandwidth of digital signals

 

4  Radio-Frequency Parameters

 

This section introduces some of the most common Radio-Frequency (RF) parameters used in the field of EMC:

reflection parameter s11

 

 

Reflection Coefficient Γ.

We speak of matched impedances in case the load impedance Zload is the complex conjugate of the source impedance Zsource. In radiated emission and immunity EMC testing, it is important to understand the term matching and how to quantify it. All receiver and/or transmitter antennas must be matched to their receiver and/or transmitter equipment impedance (typical Z= 50Ω).

The reflection coefficient Γ (=s11 in case of 1-port networks!) is defined as [4.4]:

reflection coefficient

 

All variables are complex numbers. Vforward is the forward voltage wave to the load and Vreflection is the reflected voltage wave by the load. Zsource is the complex source impedance and Zload is the complex load impedance. Zsource is typically the characteristic impedance Z0 or the transmission line impedance. The reflection coefficient Γ is often given in [dB]:

reflection coefficient dB

 

 

VSWR.

VSWR means Voltage Standing Wave Ratio. The VSWR expresses the ratio of the maximum voltage Vmax [V] of a standing voltage wave pattern and the minimum voltage of a standing wave pattern Vmin [V] on a transmission line. A VSWR value of 1.0 means perfectly matched. A VSWR value of infinity means complete mismatch (100% of the forward wave is reflected). The VSWR can be calculated by using the reflection coefficient from above [4.5]:

VSWR formula
VSWR.PNG

 

 

Return Loss.

The return loss [dB] is the dB-value of the loss of power in the signal reflected (Preflected) by a discontinuity in a transmission line or due to an impedance mismatch. A low RL value indicates that not much power is transferred to the load and is reflected instead. Return loss [dB] is the negative value of the reflection coefficient Γ in [dB] [4.6].

return loss formula dB
return loss

Insertion Loss [dB].

The term Insertion Loss (IL) is generally used for describing the amount of power loss due to the insertion of one or several of the following components (passive 2-port networks):

  • Transmission Line (cable, PCB trace)

  • Connector

  • Passive Filter

Insertion Loss

 

The insertion loss (IL) represents the power ratio in [dB] of the power P1 and the power P2  of the picture above. P1 is the power, which would be transferred to the load in case the source is directly connected to the load. The power P2 represents the power which is transferred to the load in case the Passive 2-Port Network is inserted between the source and the load [4.2], [4.3].

InsertionLoss_Formula.PNG

 

 

Scattering Parameters (S-Parameters).

Scattering Parameters} - also called S-parameters - are commonly used in high-frequency or microwave engineering to characterize a two-port circuit (see the picture below). The scattering parameters describe the relation of the power wave parts a1, b1, a2, and b2 that are transferred and reflected from a two-ports input and output. The physical dimension for the incident a and reflected b power waves is not Watt, it is √Watt.

Scattering Parameters, S-Parameters

 

Generally speaking, the S-parameter sij is determined by driving port j with an incident wave of voltage Vj+ and measuring the outgoing voltage wave Vi- at port i. Considering the picture above, the four scattering parameters can be computed as follows:

Scattering Parameters Formulas
4 - RF Parameters
Reflection coefficient
VSWR
Return loss
Insertion loss
Impedance matching summary
S-Paramters

 

5  Transmission Lines

 

In EMC, it is essential to understand transmission lines and when to apply the concept of transmission lines. Why? Because once a signal interconnection line exceeds a critical length lcritical [m], impedance matching (Zsource, ZlineZload) MUST be considered to prevent reflections and ringing, thus preventing unwanted radiated emissions and bad signal quality - a signal integrity topic [5.2].

This chapter introduces you to transmission lines and their most important properties.

What is a transmission line?

A transmission line is a series of conductors, often but not necessarily two, used to guide electromagnetic energy from one place to the other [5.3]. It's that simple. The more complicated part is the math behind it (Maxwell's equations) because we do no longer consider a conductor as a lumped element (e.g. a simple R-L series circuit to emulate an electrical interconnection). Rather, we consider the signal conductor as a transmission line through which an electromagnetic field is moved from one point to another. Transmission lines are characterized or described by their characteristic impedance Z0.

Here are some common transmission line geometries [5.3]:

Transmission lines: Coax, Microstrip, Stripline, Balanced Line, Waveguide

  • Coax. The electromagnetic energy is propagating through the dielectric (mostly PTFE, because of its low loss and stable εr for many frequencies) between the center conductor and the inside surface of the outer conductor (shield) of a coaxial cable.

  • Microstrip. Transmission line where the signal conductor is on the top or bottom layer of a PCB with an adjusted return path conductor (e.g. ground plane or power supply plane).

  • Stripline. Transmission line where the signal conductor is embedded between two signal return path conductors (e.g. ground or power supply plane) on a PCB.

  • Balanced line. Two conductors of the same size and shape with equal impedance to ground and all other conductors (e.g. ethernet cable).

  • Waveguide. A waveguide consists of a single hollow conductor used to guide the electromagnetic energy. Waveguides are used in the gigahertz frequency range and they cannot pass direct currents (DC) signals.

 

 

When to consider a signal path as a transmission line?

Every signal interconnection is a transmission line. However, it is not necessary to threat every signal path as a transmission line. Rules of thumb - if a conductor should be treated as a transmission line or not - are mentioned below: one rule of thumb for the frequency domain and one for the time domain.

 

Frequency domain. A common rule of thumb, when working in the frequency domain, is the following [5.3]:

  • Interconnection length llong  ≥ λ/10. Consider the signal path as a transmission line, in order to minimize signal distortions and ringing due to reflections and in order to minimize radiated emissions and electromagnetic interference (EMI).

  • Interconnection length lshortλ/10. Consider the signal path as a simple conductor. If an interconnection length l [m] is short with respect to the signal wavelength λ [m], it is good practice that the interconnection is considered as a simple conductor with lumped-element parameters (e.g. resistor R [Ω] in series with inductance L [H]).

When determining the shortest wavelength λmin [m] in a digital signal (e.g. clock), it is necessary to know the maximum frequency fmax [Hz] of the signal by considering the rising- and falling-times (rather than the fundamental frequency). The rule of thumb for calculating the bandwidth [Hz] - or the highest significant sine wave frequency - of a rectangular digital signal is [5.1]:

bandwidth (maximum frequency) of digital signals

Where t10%-90% is the rising- or fall-time (whichever is smaller) from 10% to 90% of the slope of a digital signal in [sec]. The corresponding minimum wavelength λmin [m] is

WavelengthForFmax.PNG

Where v [m/sec] is the propagation velocity and fmax [Hz] is the highest significant sinusoidal frequency in a digital signal. The frequency domain approximation for the critical length lcritical-fd [m] can be calculated with respect to the digital signal rise-/fall-time t10%-90%:

Critical length of transmission line in frequency domain

Where c [m/sec] is the speed of light (3E8m/sec), fmax [Hz] is the highest significant sinusoidal frequency in the digital signal, t10%-90% [sec] is the rising- or fall-time (whichever is smaller) from 10% to 90% of the slope of the digital signal and εreff [1] is the effective dielectric constant (relative permittivity) through which the electromagnetic wave is propagating.

Time domain. There is also a rule of thumb for the time domain [5.3]:

  • t10-90% ≤ 2*tpd. If the rise- or fall-time t10-90% [sec] of a digital signal is smaller than twice the propagation delay tpd [sec] (along the signal line), then the signal path should be considered as transmission line, in order to minimize signal distortions and ringing due to reflections and in order to minimize radiated emissions and electromagnetic interference (EMI).

  • t10-90% > 2*tpd. If the rise- and fall-time t10-90% [sec] of a digital signal are bigger than twice the propagation-delay tpd [sec] of the signal across the conductor, the signal path may be considered as simple conductor.

The time domain approximation for the critical length lcritical-td [m] can be calculated with respect to the digital signal rise-/fall-time t10%-90%:

Critical length of transmission lines in the time domain

Where c [m/sec] is the speed of light (3E8m/sec), t10%-90% [sec] is the rising- or fall-time (whichever is smaller) from 10% to 90% of the slope of the digital signal and εreff [1] is the effective dielectric constant (relative permittivity) through which the electromagnetic wave is propagating.

 

Critical length lcritical. The two rules above lead to similar values for lcritical [m], where the frequency domain lcritical-fd is smaller than the time domain lcritical-td. It is therefore recommended to go with the rule of thumb of the frequency domain: Consider an interconnection as transmission line if it is longer than λ/10.

Critical length of signal line

 

Characteristic Impedance.

The characteristic impedance Z0, also called the wave impedance, is an important property of a transmission line. First, have a look at the equivalent circuit of a transmission line (the distribution parameter model of a two-conductor transmission line) [5.3]:

Characteristic impedance

 

The picture shows transmission line segments of an infinitely small length dz in [m]. The parameters are defined per unit length (e.g [m]):

  • R' = Resistance per unit length [Ω/m]

  • L' = Inductance per unit length [H/m], mostly in [mH/m] or [nH/m]

  • C' = Capacitance per unit length [F/m], mostly in [pF/m]

  • G' = Conductance per unit length [S/m]

The formula for the characteristic impedance Z0 of a transmission line is defined as [5.3]:

Characteristic imedance

 

where ω is the angular frequency [rad/sec] and all other parameters are explained above. In practice, it is often adequate to describe transmission lines as lossless (R' = 0, G' = 0). In that case, the equivalent circuit is simplified to this:

Lossless transmission line

 

The formula for the characteristic impedance Z0 of lossless transmission lines is defined as [5.3]:

Charcteristic impedance lossless

 

Enough theory, let's think about how to calculate the characteristic impedance for your projects.

  • Cables. In case your cable contains signals which require impedance matching (e.g. CAN or Ethernet), you should only use cables that match with the required impedance (e.g. 100Ω or 50Ω). In general, it is not necessary to calculate the characteristic impedance of cables, this is already done for you by the cable manufacturer.

  • PCBs. Because every PCB design is individually configurable (type of dielectric material, thickness of copper, PCB trace geometry, etc.), it is usually necessary to calculate the characteristic impedance by yourself. Therefore, you should know the following data:

    • Dielectric media. Thickness, dielectric constant εr and loss tangents tan(δ) of the PCB substrate. Have a look at our PCB stackup and dielectric material collection here.

    • Trace. PCB trace width and geometry, copper thickness, height above reference planes, distance to copper-pour (and separation distance for differential lines).

    • Solder resist. For PCB traces at top or bottom, you must know the thickness and dielectric constant of the solder resist.

There are plenty of free online and offline tools available for calculating the characteristic impedance of arbitrary PCB traces or signal pairs. However, be aware that these free tools usually use approximations and the results are only accurate in a certain parameter range. If you need accurate values use a solver, which calculates the transmission line impedance based on Maxwell's Equations (e.g. HyperLynx or Si8000). To help you even more, we wrote down some information on PCB stackups and properties of PCB materials.

 

 

Propagation Constant.

The propagation constant γ [1/m] is an important property of a transmission line. It describes the attenuation and phase shift of the signal as it propagates through the transmission line. Let's imagine a sinusoidal voltage, current, electric field, or magnetic field which propagates in the direction of the z-axis and which has an amplitude of A0 at its source and amplitude of A(z) at the distance z [m] from the source. Then A(z) can be written as:

Propagation through along transmission line

where A(z) is the complex phasor term of a sinusoidal voltage [V], current [A], electric field [V/m], or magnetic field [A/m] at the distance z [m] away from the source and γ [1/m] is the complex propagation constant. Propagation constant γ is calculated like this [5.3]:

propagation constant formula

 

where R'=resistance per unit length [Ω/m], L'=inductance per unit length [H/m], C'=capacitance per unit length [F/m], G'=conductance per unit length [S/m],  ω=angular frequency [rad] of the signal, μ=μrμ0μ0=4πE-7 [H/m] μr=relative permeability [1], εrε0, ε0=8.85E-12 [F/m] εr=relative permittivity [1].

Propagation constant γ in can also be written as [5.3]:

Propagation constant

 

where the real part α in [1/m] is the attenuation constant and the imaginary part β in [rad/m] is the phase constant. α and β are calculated like this [5.3]:

attenuation costant and phase constant formula

 

For a lossless line (R'=0, G'=0, dielectric losses = 0) we get:

  • No attenuation α [1/m]:

Attenuation lossless line

  • Phase shift β [rad/m]:

phase constant lossless line

 

A sinusoidal signal that travels along a transmission line with attenuation α > 0 [1/m] has a signal form along the z-axis that looks like this:

Transmission line attenuation constant

 

High-Frequency Losses.

The lossless line model is often accurate enough for frequencies up to 100MHz. However, above 100MHz, the high-frequency losses may not be neglected anymore, and therefore the attenuation factor α [1/m] cannot be assumed to be zero. High-frequency losses are a result of [5.3]:

  • Ohmic Loss. Resulting from the resistance of the conductors. Ohmic losses are a function of the frequency f [Hz] as well as of the geometry of the conductor (skin-effect!).

  • Dielectric Loss. Resulting from the dielectric material absorbing energy from the propagating electric field (heating the material). Dielectric losses are a function of frequency f, the dissipation factor (tan(𝛿)) and the dielectric constant (ε).
    NOTE: Dielectric losses do NOT depend on the geometry of the transmission line, only on the dielectric material.

 

Balanced vs. Unbalanced Transmission Lines.

EMC design engineers should be well aware of the concept and benefits of balanced transmission lines. Here are the differences between balanced and unbalanced transmission lines:

  • Balanced. A balanced transmission line consists of two conductors which have the same impedance along their line and the same impedance to ground and all other conductors. Differential signals should be transmitted over balanced transmission lines.

  • Unbalanced. For an unbalanced transmission line, the impedances of the forward and return current lines to ground are unequal. Single-ended signals are signals which are referenced to ground and should therefore be sent over unbalanced transmission lines.

Balanced transmission lines are very robust against common-mode noise because common-mode signals will be canceled out at the receiver's side. However, to prevent differential-mode noise coupling, the two signal conductors must be routed close to each other (e.g. by twisting them or by routing them as differential-pair on a PCB). The pictures below illustrate the common-mode noise suppression of a balanced transmission line compared to an unbalanced transmission line.

unbalanced transmission line
balanced transmission line

Generally, single-ended interfaces (CMOS, TTL, I2C, SPI) should be sent over unbalanced transmission lines, and differential signal interfaces (LVDS, USB, Ethernet, CAN, HDMI) should be sent over balanced transmission lines. Examples of balanced and unbalanced transmission lines are:

  • Unbalanced. Suitable for single-ended signal interfaces.

    • PCB data lines. Microstrip lines, striplines coplanar waveguides.​

    • Cables and wires. Coaxial cables, multilayer flat-ribbon or flat-flex cables with at least one solid ground plane

  • Balanced. Suitable for differential and pseudo-differential signal interfaces.​

    • PCB data lines. Microstrip lines and stripline routed as differential pairs.​

    • Cables and wires. Twisted pair, twin-lead cables, flat-ribbon or flat-flex cables (without ground plane).

5 - Transmission Lines
What is a transmission line?
When to consider a signal pat as a transmission line?
Characteristic Impedance
Propagation constant
High-Frequency Loss
BalancedVsUnbalanced
6 - Near/Far Field
Electromagnetic Field Characteristics
Wave and Characteristic Impedance

 

 

6  Near-Field vs. Far-Field

EMI often happens due to electromagnetic radiation (see coupling paths). In order to reduce the radiated coupling, it is important to understand the near-field and far-field.

 

Electromagnetic Field Characteristics.

An electromagnetic field is characterized by three things [6.4]:

  1. Source. The antenna (e.g. dipole/horn/loop antenna, cable, PCB trace).

  2. Media. The media surrounding the source (e.g. air, plastics, metal).

  3. Distance. The distance between the source and the observation point. Close (compared to the wavelength λ) to the source, the field properties are determined primarily by the source characteristics (wave impedance Zw). Far from the source, the field depends mainly on the medium through which the field is propagating.
    Therefore, the space around a source of radiation can be split into two regions: The near-field and the far-field.

For EMC emission measurements, it is important to know if a certain measurement takes place in the near-field or the far-field. Different probes and antennas have to be used accordingly.

  • Near-field. Special near-field probes are used to measure the H- or E-field.

  • Far-field. Log-periodic, biconical or horn antennas are used to measure the EM-field.

 

 

Wave Impedance.

Before we dive into the near- and far-field topic, we have to talk about the wave impedance. The wave impedance is the characteristic of a medium (air, transmission line dielectric medium, etc.) in which a wave propagates.

Why is it important to know the characteristic impedance? Because the ratio of reflected and transmitted amplitude of the wave at an interface, from one medium to another, is determined by the characteristic impedance of the two media.

For ANY electromagnetic wave, the wave impedance ZW in [Ω] is defined as [6.1]:

WaveImpedance.PNG

 

E is the electric field in [V/m] and H is the magnetic field in [A/m]. 

The characteristic impedance Z0 [Ω] of a medium (NOT a transmission line, here we talk about electromagnetic waves traveling through a medium like air, insulator, metal shield, etc.) is defined as [6.1]:

Characteristic Impedance

 

ω=angular frequency [rad/sec] of the signal, μ=permeability of the medium [H/m], ε=dielectric constant of the medium [F/m], σ=conductivity of the medium [S/m].

For insulators and air (σ << jωε) the characteristic impedance is independent of the signal frequency [6.1]:

Characteristic impedance insulator

 

μ=permeability of the medium [H/m], ε=dielectric constant of the medium [F/m], μ0=permeability of free-space 4πE-7 [H/m], μr=relative permeability of the media [1], ε0=dielectric constant of free-space 8,85E-12 [F/m], εr=relative dielectric constant of the media.

For free-space (and approximately for air) are: μr=1, εr=1. Therefore, the characteristic impedance of free-space (air) is defined as [6.1]:

 

Characteristic impedance free-space

 

 

Wave Impedance vs. Distance.

The graph below shows the wave impedance ZW [Ω] in dependency of the distance d [m] to the source (normalized with λ/(2*π)) for an ideal Hertzian dipole (an infinitesimal element of length dl). The graph is a simplification and it should just illustrate how the magnetic field H [A/m] and electric field E [V/m] differ in their wave impedance ZW [Ω] in the near field and that the electromagnetic field (EM-field) has a constant wave impedance ZW [6.1].

Near field vs. far field

 

 

Near-Field to Far-Field Boundary.

The electromagnetic field around an antenna can be divided in three regions [6.2]:

  1. Reactive near-field

  2. Radiating near-field
  3. ​Far-field

The regions depend on the maximum linear dimension of the antenna D [m] and the wavelength of the signal λ [m]:

  • D<λ/2. Electrically small antennas. The reactive near-field is significant. For electrically small antennas, the radiating near-field and the far-field are minimal if they exist at all.

  • D>λ/2. Electrically large antennas. All three regions are significant: the reactive near-field, the radiating near-field and the far-field.

NearField_Reactive_SmallAntenna.PNG
Near-field to far-field boundary for electrically large antennas.

 

 

Near Field.

In the near field, the characteristic impedance depends primarily on the source and the electric and magnetic fields have to be considered separately (because the ratio of E/H is not constant).

  • The electric field E is predominant in these cases [6.3]:

    • The source voltage is high compared to the source current (E/H > 377Ω).​

    • The source impedance is high (e.g. dipole or straight wire antennas).

  • As a consequence of a predominant E-field:​​​​

    • The wave impedance near the antenna is high.

    • E-field attenuates with a rate of 1/d^3 in the near field (d = distance to source).

    • H-field attenuates with a rate of 1/d^2 in the near field (d = distance to source).

  • The magnetic field H is predominant in these cases [6.3]:

    • The source voltage is low compared to the source current (E/H < 377Ω).​

    • The source impedance is low (e.g. loop antennas).

  • ​As a consequence of a predominant H-field:

    • The wave impedance near the antenna is low.

    • E-field attenuates with a rate of 1/d^2 in the near field (d = distance to source).

    • H-field attenuates with a rate of 1/d^3 in the near field (d = distance to source).

As mentioned above, the near-field can be divided into the following two regions:

  • Reactive Near-Field. In the reactive near-field, energy is stored in the electric and magnetic fields very close to the source, but not radiated from them. Instead, energy is exchanged between the signal source and the fields. In case of D<λ/2, the reactive near-field extends until the distance d [m] from the antenna by [6.2]:

Near-field boundary for electrically small antennas.

where λ is the wavelength [m] of the signal. In case of D>λ/2, the reactive near-field extends until the distance d [m] from the antenna by [6.2]:

Reactive near-field boundary for electrically small antennas.

 

where λ is the wavelength [m] of the signal and D the maximum linear dimension of the antenna [m].